This series of power transformer is a energy-saving product with high technology and performance, which reaches international advanced level of same type transformer. The transformer core adopting high permeability is wounded into enclosed type, and there will be no butt joint, annealing process of core can comb-out internal stress, and there is no high magnetic zone in magnetic circuit, thus sharp decreasing no-load loss and magnetic current. Comparing with S9 type power transformer, its capacity is down 30%, no-load current is down 70%, and the sound level is down 10dB. The transformer adopting full-sealing structure cancels conservator, thus isolating oil from external gas, in this case, the insulation is not easy to damp and the degree of aging is reduced, thus improving the reliability and operation life.

Full-sealing oil-immersed distribution transformer with wound core

type Voltage combination and tap range
(KW)
Vector group
No-load loss
(KW)
On-load loss
(KW)
No-load current
(%)
Short circuit impedance(%) Total weight
(kg)
Overall dimension(mm) Traction gauge(mm)
HV Tap range of HV LV (L) (W) (H)
S11-M-R-30 6
6.3
10
10.5
11
±5% or
±2×2.5%
0.4
0.69
Yyn0 or
Dyn11
0.10 0.60 1.00 4.0 350 1040 640 990 400×400
S11-M-R-50 0.13 0.87 0.90 440 1080 640 1050
S11-M-R-63 0.15 1.04 0.80 510 1110 650 1100
S11-M-R-80 0.18 1.25 0.70 550 1130 660 1150
S11-M-R-100 0.20 1.50 0.60 650 1150 660 1210
S11-M-R-125 0.24 1.80 0.60 730 1180 670 1250
S11-M-R-160 0.27 2.20 0.55 810 1200 680 1280 550×550
S11-M-R-200 0.33 2.60 0.55 960 1250 700 1390
S11-M-R-250 0.40 3.05 0.50 1110 1310 720 1420
S11-M-R-315 0.48 3.65 0.50 1310 1390 770 1480
S11-M-R-400 0.57 4.30 0.45 1630 1460 800 1550 660×660
S11-M-R-500 0.68 5.10 0.45 1880 1490 810 1620
S11-M-R-630 0.81 6.20 0.40 4.5 2280 1580 840 1700

(1)Above parameter is suitable for 4010KV transformer.

(2)The overall dimension and weight are reference only, and we have a right to change them.

(3)W can produce the transformer with special performance parameter according to requirements of users.

 

 