Railway traction

total of x / x pictures

Product characteristic:
The transformer which can supply power for rail traction system is called rail traction transformer. We adopt advanced design technology and manufacturing process in the world, as well as programmable design, via analysis and quantitative calculation for insulating breakdown mechanism, numerical analysis of electric field, impact characteristic and strength of withstanding sudden short circuit of insulating technology and winding, and combine with many years of manufacturing experience, making our product have a big breakthrough based on conventional technology, thus improving the reliability and advancement of our transformers. And our products have many excellent technical performances such as low temperature rise, low loss and sound level with high efficiency and outstanding ability of withstanding short-circuit and overload.

110kV voltage classes

(1)110kV three phase“V,v” rail traction transformer

Rated power(kVA)
AB+BC
Rated voltage (kV)
Vector group
No-load loss
(kW)
Load loss
(kW)
No-load current
(%)
Short circuit impedance(%)
Overall dimension
(L×W×H)
Primary side
Secondary side
6300+10000
110士2×2.5%
2×27.5
Vv0
or
Vv6
15
70
0.6
8.4or10.5
5750×4300×4400
8000+10000
17
82
0.6
5800×4500×4500
10000+10000
19
90
0.5
5850×4650×4600
10000+12500
20
100
0.5
5850×4700×4700
12500+12500
23
105
0.5
5900×4750×4750
12500+16000
25
110
0.5
6000×4950×4900
16000+16000
27
115
0.5
6050×5200×5050
16000+20000
28
120
0.5
6100×5350×5200
20000+20000
29
128
0.5
6150×5500×5350
20000+25000
34
140
0.5
6200×5750×5500
25000+25000
37
145
0.5
6250×5900×5700
25000+31500
42
160
0.5
6300×6050×5950
31500+31500
47
175
0.5
6350×6200×6050

Note: the design of rated power, rated voltage, vector group and performance parameter can be based on requirement of user.

(2)110kV three phase“V,x” rail traction transformer

Rated power(kVA)
AB+BC
Rated voltage (kV) Vector group No-load loss
(kW)
Load loss
(kW)
No-load current
(%)
Short circuit impedance(%) Overall dimension
(L×W×H)
Primary side Secondary side
6300+10000 110士2×2.5%
2×27.5
I,i0,i6+?I,i0,i6
19.5 88 0.6 8.4or10.5 7100×3800×4000
8000+10000 22 102 0.6 7200×3950×4150
10000+10000 25 112 0.5 7300×4000×4250
10000+12500 26 125 0.5 7350×4000×4350
12500+12500 30 132 0.5 7400×4100×4500
12500+16000 32.5 137 0.5 7500×4150×4600
16000+16000 35 144 0.5 7600×4300×4750
16000+20000 36.5 150 0.5 7650×4400×4850
20000+20000 38 160 0.5 7700×4550×5000
20000+25000 44 170 0.5 7750×4650×5150
25000+25000 48 184 0.5 7800×4800×5300
25000+31500 55 200 0.5 7850×5000×5450
31500+31500 61 219 0.5 7900×5150×5600

Note: the design of rated power, rated voltage, vector group and performance parameter can be based on requirement of user.

220kVvoltage classes

(1)220kV single phase“V,v” rail traction transformer,two sets single rail traction transformer external connection“V,v”

Rated power(kVA)
AB+BC
Rated voltage (kV)
Vector group
No-load loss
(kW)
Load loss
(kW)
No-load current
(%)
Short circuit impedance(%)
Overall dimension
(L×W×H)
Primary side
Secondary side
20000+20000
110士2×2.5%
27.5
Vv0
or
Vv6
42
140
0.60
10.5or12.0
7000×3600×3900
20000+25000
46
153
0.60
7100×3700×4000
25000+25000
50
166
0.5
7200×3750×4100
25000+31500
54
182
0.5
7250×3850×4200
31500+31500
58
198
0.5
7300×3900×4300
31500+40000
64
217
0.5
7400×4050×4400
40000+40000
70
236
0.5
7500×4200×4550
40000+50000
76
253
0.5
7550×4300×4650
50000+50000
82
280
0.5
7600×4450×4800
50000+60000
88
305
0.5
7650×4550×5000
60000+60000
95
330
0.5
7700×4700×5100

Note: the design of rated power, rated voltage, vector group and performance parameter can be based on requirement of user.

(2)220kV three phase“V,v” rail traction transformer

Rated power(kVA)
AB+BC
Rated voltage (kV)?(kV) Vector group No-load loss
(kW)
Load loss
(kW)
No-load current
(%)
Short circuit impedance (%) Overall dimension
(L×W×H)
Primary side Secondary side
12500+12500 220士2×2.5% 2×27.5 Vv0
or
Vv6
26.5 119 0.90 10.5or12.0 5550×5300×7350
12500+16000 28 121 0.80 5600×5450×7500
16000+16000 31 122 0.70 5650×5600×7625
16000+20000 32.5 124 0.70 5700×5750×7800
20000+20000 36 126 0.60 5750×5950×7950
20000+25000 39 138 0.60 5800×6000×6050
25000+25000 43 149 0.5 5850×6150×6200
25000+31500 45 164 0.5 5900×6300×6350
31500+31500 48 178 0.5 5950×6450×6500
31500+40000 51 195 0.5 6000×6600×6650
40000+40000 54 212 0.5 6050×6750×6800
40000+50000 57 228 0.5 6100×6900×6950
50000+50000 59.5 252 0.5 6150×7050×7150
50000+60000 62 275 0.5 6200×7100×7200
60000+60000 65.5 297 0.5 6300×7250×7400

Note: the design of rated power, rated voltage, vector group and performance parameter can be based on requirement of user.

(3)220kV single phase“V,x” rail traction transformer,two sets single rail traction transformer external connection “V,x”

Rated power(kVA)
AB+BC
Rated voltage (kV) Vector group No-load loss
(kW)
Load loss
(kW)
No-load current
(%)
Short circuit current
(%)
Overall dimension
(L×W×H)
Primary side Secondary side
20000+20000 220士2×2.5% 2×27.5 I,i0,i0+?I,i0,i0or
I,i0,i6+?I,i0,i6
42 154 0.60 10.5
or
12.0
7650×5150×7500
20000+25000 46 168 0.60 7700×5250×7650
25000+25000 50 184 0.5 7750×5350×7800
25000+31500 54 200 0.5 7800×5500×7900
31500+31500 58 218 0.5 7850×5650×8000
31500+40000 64 239 0.5 7900×5800×8150
40000+40000 70 260 0.5 8000×6000×8300
40000+50000 76 278 0.5 8050×6100×8450
50000+50000 82 308 0.5 8100×6250×8600
50000+60000 88 336 0.5 8200×6400×8700
60000+60000 95 363 0.5 8300×6550×8850

Note: the design of rated power, rated voltage, vector group and performance parameter can be based on requirement of user.

(4)220kV three phase“V,x” rail traction transformer

Rated power(kVA)
AB+BC
Rated voltage (kV) Vector group No-load loss
(kW)
Load loss
(kW)
No-load current
(%)
Short circuit impedance(%) Overall dimension
(L×W×H)
Primary side Secondary side
12500+12500 220士2×2.5% 2×27.5 I,i0,i0+?I,i0,i0or
I,i0,i6+?I,i0,i6
26.5 131 0.90 10.5or 12.0 10750×5200×6050
12500+16000 28 133 0.80 10800×5300×6200
16000+16000 31 135 0.70 10850×5400×6350
16000+20000 32.5 137 0.70 10900×5500×6500
20000+20000 36 139 0.60 10950×5650×6650
20000+25000 39 152 0.60 11000×5800×6800
25000+25000 43 166 0.5 11050×5950×6900
25000+31500 45 180 0.5 11100×6050×7000
31500+31500 48 196 0.5 11150×6200×7100
31500+40000 51 215 0.5 11200×6350×7250
40000+40000 54 234 0.5 11250×6500×7400
40000+50000 57 250 0.5 11300×6650×7550
50000+50000 59.5 277 0.5 11350×6800×7650
50000+60000 62 302 0.5 11400×6950×7800
60000+60000 65.5 327 0.5 11500×7100×7950

Note: the design of rated power, rated voltage, vector group and performance parameter can be based on requirement of user.

automatic railway special transformer

Rated power(kVA) Rated voltage (kV) No-load loss
(kW)
Load loss
(kW)
Short circuit impedance(Ω) Overall dimension
(L×W×H)
Primary side Secondary side
6250/12500 2×27.5 27.5 6.3 25 0.45±
10%
3500×3200×3500
8000/16000 7.5 30 3500×3350×3600
10000/20000 9 36 3600×3500×3700
12500/25000 11 41 3700×3650×3800
16000/32000 14 49 3800×3800×3900
20000/40000 16.5 58 3900×3950×4000
25000/50000 19.5 69 4000×4100×4100

 

 

 

 

 

 

 

 

 

 

 

 

 