KV type on-load tap changer is combination type tap changer, which is basis of optimization design of domestic V type tap change. It gathers switchover and selection function, and is divided into roof type that is suitable for roof type transformer and bell type that is suitable for bell type transformer.
The tap changer that is driven by KDJ-II electrical motor mechanism realize the conversion of transformer taps. It equipped with KYC-3D intelligent gears displayer to indicate the tap position and operation control; while equipped with KYJK-1/2 intelligent controller to display the tap position, and perform remote control, automatically voltage regulation and operation control in parallel of several transformer. The product is suitable for using for power transformer or industrial transformer with on-load voltage regulation output voltage, whose rated voltage is 35kV~110kV, maximum rated through current is 500A for three phases, 700A for single phase, frequency is 50Hz and maximum step voltage is 1650V, which can performance transformer voltage regulation on any tap position, and is suitable for following voltage regulation method: such as linear, reverse and coarse/fine.

Technical Data Sheet

KV Type On-load tap changer Technical Data Sheet

Serial No. Description KVIII350 KVIII500 KVI700
1 Maximum rated through current/A 350 500 700
2 Rated frequency/Hz 50-60
3 Phase number and connection method 任意连接
4 Maximum step voltage/V 10 contact 1650
12 contact 1400
14 contact 1000
5 Rated step power /kVA 10 contact 525 525 660
12 contact 420 420 520
14 contact 350 350 450
6 Withstand short-circuit ability/kA Thermal stability/3s effective value 5 7 10
Dynamic stability/peak value 12.5 12.5 25
7 Tap position number Standard design: maximum 13 for linear, maximum 27 for reverse/coarse/fine
8 Main insulation level/kV Equipment highest voltage 40.5 72.5 126*
Power frequency voltage (50Hz1min) 85 140 230
Impact withstand voltage(1.2/50μs) 200 350 550
9 Internal insulation level/k(impact/power frequency) a:between maximum tap and minimum tap 10 contact:200/50 14 contact:170/50
b:between any tap Yconnection 200/70
Dconnection 40.5kV:225/85???????40.5kV:350/140
c:coarse phase-phase 350/140
d:same phase coarse 200/53
10 mechanical life >800000
11 electric life >200000
12 Oil compartment operation pressure 30kPa
sealing performance No leakage for 60 kPa 24h and 133Pa vacuum
overpressure protection Blasting cover will blast for overpressure of 300±20% kPa
Gas relay Setting oil speed 1m/s±10%
13 With electric motor mechanism KDJ-II

Note:* means special design