66kV oil-immersed power transformer

total of x / x pictures

(1)reasonable construction: use modern computer technology to analyze the characteristic about electric, magnetic, force and thermal for transformer, and on this basis to design construction drawings, making product construction be more reasonable and completed.
(2) advanced performance: in addition to that product performance can meet relevant national standard, special design can also perform as per user requirement and PD level is obviously less than specified value of national standard.
(3) safe and reliable: Winding insulation structure, ampere-turn arrangement and cooling system are designed on basis of analysis for transformer electric, magnetic, force and thermal performance, improving transformer ability to withstand over-voltage and short-circuit current and the local overheating does not occur.
(4) high quality components: select high quality components from domestic or abroad as per user requirement, making product performance will be more reliable.
(5) worry-free for user: beautiful appearance, no leakage and free- untanking.

S(F)11- 66KVtwo windings, off-load voltage regulation transformer

Rated
power(KVA)
Voltage combination Vector group Short circuit impedance(%) No-load loss(KW) Load loss(KW) No-load
current(%)
Overall dimension(mm)(L×W×H)
High voltage(KV) Low voltage(KV)
630 66±2×2.5% 6.3
10.5
Yd11 8 1.3 7.1 1.40 4200×3320×3510
800 1.5 8.6 1.35 4280×3380×3560
1000 1.8 9.9 1.30 4320×3400×3600
1250 2.1 12.0 1.30 4490×3430×3660
1600 2.5 14.1 1.25 4500×3450×3740
2000 2.9 16.6 1.20 4540×3440×3800
2500 3.4 19.7 1.10 4600×3460×3840
3150 YNd11 4.1 23.1 1.05 4630×3480×3870
4000 4.8 27.4 1.00 4690×3860×3900
5000 5.8 30.8 0.85 4700×3500×3870
6300 9 7.4 34.2 0.75 4730×3560×3950
8000 9.0 40.6 0.75 4770×3610×4070
10000 10.6 47.9 0.70 5200×4020×4280
12500 12.5 56.8 0.70 5260×4060×4310
16000 15.0 69.8 0.65 5420×4120×4340
20000 17.6 84.6 0.65 5500×4140×4430
25000 20.8 100.0 0.60 5700×4620×4600
31500 24.6 120.6 0.55 5850×5000×4700
40000 29.4 141.5 0.55 6000×5400×5000
50000 35.2 175.3 0.50 6200×5400×5100
63000 41.6 211.2 0.45 6300×5560×5330

Transformer outline drawing

(4)S(F)Z11- 66KV two windings, on-load voltage regulation transformer

Rated
power(KVA)
Voltage combination Vector group Short circuit impedance(%) No-load loss(KW) Load loss(KW) No-load
current(%)
Overall dimension(mm)(L×W×H)
High voltage(KV) Low voltage(KV)
6300 66±8×1.25% 6.3
10.5
YNd11 9 8.0 34.2 0.75 5500×3670×3600
8000 9.6 40.6 0.75 5540×3710×3650
10000 11.4 47.9 0.70 5540×3780×3650
12500 13.4 56.8 0.70 5560×4600×4100
16000 16.2 69.8 0.65 5600×4600×4200
20000 19.2 84.6 0.65 5670×4700×4200
25000 22.7 100.0 0.60 6150×4860×4480
31500 27.0 120.6 0.55 6240×4980×4910
40000 32.2 141.5 0.55 6320×4980×5240
50000 38.1 175.3 0.50 6900×5430×5250
63000 45.0 211.2 0.45 7000×5500×5300

Transformer outline drawing

 

 

 

 

 