110kV oil-immersed power transformer

total of x / x pictures

(1)reasonable construction: use modern computer technology to analyze the characteristic about electric, magnetic, force and thermal for transformer, and on this basis to design construction drawings, making product construction be more reasonable and completed.
(2) advanced performance: in addition to that product performance can meet relevant national standard, special design can also perform as per user requirement and PD level is obviously less than specified value of national standard.
(3) safe and reliable: Winding insulation structure, ampere-turn arrangement and cooling system are designed on basis of analysis for transformer electric, magnetic, force and thermal performance, improving transformer ability to withstand over-voltage and short-circuit current and the local overheating does not occur.
(4) high quality components: select high quality components from domestic or abroad as per user requirement, making product performance will be more reliable.
(5) worry-free for user: beautiful appearance, no leakage and free- untanking.

S(F)11- 110KV two windings, off-load voltage regulation transformer

Rated power(KVA) Voltage combination Vector group Short circuit impedance(%) No-load loss(KW) Load loss(KW) No-load
current(%)
Overall dimension(mm)(L×W×H)
High voltage(KV) Low voltage(KV)
6300 110
121
±2×2.5%
6.3
10.5
YNd11 10.5 7.4 34.2 0.77 4960×4210×4540
8000 9.0 42.75 0.77 4970×4230×4560
10000 10.6 50.35 0.72 4970×4230×4710
12500 12.5 59.85 0.72 5300×4200×4800
16000 15.0 73.15 0.67 5350×4350×4800
20000 17.6 88.35 0.67 5500×4350×4860
25000 20.8 104.50 0.62 5700×4370×5050
31500 24.6 126.35 0.60 5780×4500×5100
40000 29.4 148.20 0.56 5900×4820×5150
50000 35.2 184.30 0.52 6200×5100×5380
63000 41.6 222.30 0.48 6170×5560×5500
75000 12~14 47.2 264.10 0.42 6190×5620×5700
90000 54.4 304.00 0.38 6200×5660×5750
120000 67.8 377.15 0.34 6500×5640×5800
150000 80.2 448.40 0.30 8600×5910×5800
180000 90.0 505.40 0.25 9000×6080×5750

Transformer outline drawing

(6)S(F)S11- 110KV three windings, off-load voltage regulation transformer

Rated power(KVA) Voltage combination Vector group Short circuit impedance(%) No-load loss(KW) Load loss(KW) no-load
current(%)
Overall dimension (mm)(L×W×H)
High voltage(KV) Medium voltage(KV) Low voltage(KV)
6300 110
121
±2×2.5%
35
38.5
6.3
10.5
YNyn0d11 17.5~18.5?10.5????6.5 9.0 44.65 0.82 6640×3890×4100
8000 10.6 53.20 0.78 6850×4100×4230
10000 12.6 62.70 0.74 6920×4160×4290
12500 14.7 74.10 0.70 7060×4230×4360
16000 17.9 90.25 0.66 7200×4470×4450
20000 21.1 106.40 0.65 7250×4510×4530
25000 24.6 126.35 0.60 7460×5050×4690
31500 29.4 149.15 0.60 7300×5170×4800
40000 34.9 179.55 0.55 7710×5120×5040
50000 41.6 213.75 0.55 7550×5440×5150
63000 49.3 256.50 0.50 8100×5230×5270

Transformer outline drawing

(7)S(F)Z11- 110KVtwo windings, on-load voltage regulation transformer

Rated power(KVA) Voltage combination Vector group Short circuit impedance(%) No-load
loss(KW)
Load loss(KW) No-load
current(%)
Overall dimension(mm)
(L×W×H)
High
voltage(KV)
Low voltage(KV)
6300 110
121
±8×1.25%
6.3
10.5
YNd11 10.5 8.0 34.20 0.80 6400×4050×4470
8000 9.6 42.80 0.80 6500×4100×4600
10000 11.4 50.40 0.74 6580×4150×4680
12500 13.4 59.90 0.74 6590×4200×4750
16000 16.2 73.20 0.69 6610×4360×4810
20000 19.2 88.40 0.69 6670×4370×4870
25000 22.7 104.50 0.64 6930×4410×5270
31500 27.0 126.40 0.64 6950×4510×5390
40000 32.3 148.20 0.58 7000×4590×5400
50000 38.2 184.30 0.58 7250×5460×5410
63000 45.4 222.30 0.52 7420×5820×5425

Transformer outline drawing

(8)S(F)SZ11-110KV three-winding, on-load voltage regulation transformer

Rated power (KVA) Voltage combination Vector group Short cicuit impedance(%) No-load loss(KW) Load loss(KW) No-load current(%) Overall dimension(mm) (L×W×H)
HV(KV) MV(KV) LV(KV)
6300 110?121?±8×1.25% 35
38.5
6.3
10.5
YNyn0d11 17.5~18.5?10.5????6.5 9.6 44.70 0.95 7040×4090×4380
8000 11.5 53.20 0.95 7180×4200×4560
10000 13.7 62.70 0.89 7250×4260×4700
12500 16.2 74.10 0.89 7150×4300×4900
16000 19.4 90.30 0.84 7200×4330×5000
20000 22.9 106.40 0.84 7210×4360×5210
25000 27.0 126.40 0.78 7315×4400×5420
31500 32.2 149.20 0.78 7450×5000×5210
40000 38.6 179.60 0.73 7780×5610×5200
50000 45.5 213.80 0.73 7900×5650×5290
63000 54.2 256.50 0.67 8000×5760×5520

Transformer outline drawing

(9)S(F)11-110KV(low voltage for 35KV)two windings, off-load voltage regulation transformer

Rated power(KVA) Voltage combination Vector group Short circuit impedance(%) No-load loss(KW) Load loss(KW) No-load current(%) Overall dimension (mm)(L×W×H)
HV(KV) LV(KV)
6300 110
121
±2×2.5%
35
38.5
YNd11 10.5 8.0 37.10 0.84 5170×3270×3880
8000 9.6 44.70 0.84 5220×3570×3920
10000 11.2 52.30 0.78 5340×3770×4010
12500 13.1 62.70 0.78 5410×3920×4030
16000 15.7 77.00 0.72 5480×4010×4140
20000 18.6 94.10 0.72 5510×4230×4240
25000 21.9 110.20 0.67 5750×4290×4210
31500 25.9 133.00 0.67 5860×4370×4560
40000 30.9 155.80 0.61 6000×4880×5010
50000 37.0 193.80 0.61 6030×5040×5020
63000 43.7 232.80 0.56 6240×5130×5240

Transformer outline drawing

 

 